Differential pressure throttling device installation details and precautions

The differential pressure flowmeter is a meter that measures flow based on the differential pressure generated by a flow detection element installed in a pipeline, a known fluid condition, and the geometry of the detection element and the pipeline. The differential pressure flowmeter consists of a primary device (test piece) and a secondary device (differential pressure conversion and flow display instrument). The differential pressure flowmeters are usually classified based on the type of test piece , such as hole pull flowmeter, venturi flowmeter, and constant velocity tube flowmeter.

Differential Pressure Flowmeter Installation Requirements:

1, the flowmeter should be concentric with the pipeline.
2, the gasket must be concentric with the pipe and cannot protrude from the pipe.
3, The highest height of the two pressure guiding pipes should be the same.
4, to take pressure on the root valve (stop valve).
5, antifreeze.
Differential Pressure Flowmeter Installation Details:
First of all, see if you are measuring gas, liquid or steam. Gas pressure is preferably in the upper part of the pipeline; liquid pressure in the side but not immediately below the pressure, the sediment will block the pressure of the mouth; steam, then take the pressure in the side of the pipeline;
2. Do not make mistakes in the direction of the orifice plate. The mark "+" is positive, "-" is negative, and "+" is the direction that faces the fluid.
3. The positive and negative pressure taps leading to the pressure tube should be kept parallel in all cases;
4. Orifice plates are generally used with differential pressure transmitters. When connecting a pressure-conducting tube to a differential pressure transmitter, note that the positive and negative pressure should not be installed in reverse. "H" is positive and "L" is negative;
5. When measuring the gas, the differential pressure device is recommended to be placed above the pipe. If the liquid is on the bottom of the pipe, measure the steam. If there is a condensation tank, keep the condensation tank at the same level.
6. Forget straight pipe requirements, the orifice plate should have a calculation book, you find that there is a straight pipe length required to calculate the mounting hole plate before and after the installation, preferably according to that, if you can not find, you can follow the front 20D after 10D to install (D refers to the aperture plate)

Aluminium Battery Tray For New Energy Vehicles

An aluminium battery tray is a component used in vehicles to hold the battery securely in place. It is typically made of lightweight and durable aluminium material, which makes it resistant to corrosion and damage from exposure to harsh weather conditions. The tray is designed to fit the specific dimensions of the battery and is mounted to the vehicle's chassis using bolts or other fasteners. The tray helps to prevent the battery from moving around during vehicle operation, which can cause damage to the battery and other components. It also provides a secure and stable mounting point for the battery, ensuring reliable electrical connections and optimal performance.20230429100638 Png20230429100614 Png